Deep Sea Generator Set Control Module DSE5220
![]() Deep Sea Generator Set Control Module DSE5220 |
Product Description
Deep Sea Generator Set Control Module DSE5220
The DSE5220 is an automatic mains failure control module designed to provide advanced load share functionality for diesel and gas generating sets that include non-electronic/electronic engines. The module also provides excellent engine monitoring and protection features. The module monitors the mains (utility) supply and upon detection of a loss in power automatically starts the generating set.
The module's synchronizing functions include automatic synchronizing with built in synchroscope and closing onto dead bus. Direct and flexible outputs from the module are provided to allow connection to the most commonly used speed governors and automatic voltage regulators (AVRs).
The module has the ability to monitor under/over generator volts, over current, under/over generator frequency, under speed, over speed, charge failure, emergency stop, low oil pressure, high engine temperature, fail to start, low/high DC battery volts, fail to stop, generator short circuit protection, reverse power, generator phase rotation error, earth fault protection, loss of speed signal, fail to open, fail to close, out of sync, MPU open circuit failure, negative phase sequence and loss of excitation.
FEATURES
Electronic engine capability
RS232 or RS485 remote communications
Modbus RTU
Pin number protected front panel programming
Engine exercise timer
Back-lit LCD 4-line text display
Multiple language options
Voltage measurement
Configurable inputs (9)
Configurable outputs (5)
Automatic start
Manual start
Audible alarm
LED indicators
Built-in governor and AVR control for easy operation and panel engineering
Engine history event log
Engine protection
Fault condition notification to a designated PC
Front panel mounting
PC configuration
Mains (utility) failure detection
Configurable alarm timers
Configurable start & stop timers
Automatic load transfer
SMS alert messaging
Multi set communications
Front panel mounting
Remote control and monitoring.
| DC Supply |
Continuous voltage rating : 8V to 35V |
|
Cranking dip protection : Able to survive 0V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V. This is achieved without the need for internal batteries |
|
|
Charge Fail/ Excitation: 0V to 35V fixed power source 25W |
|
|
Max. Standby Current: 375mA at 12V. 200mA at 24V. |
|
|
Max. Operating Current: 460mA at 12V. 245mA at 24V |
|
| Alternator Input |
Range: 5V - 277(ph-N) (+20%) 50Hz - 60Hz (Minimum 15V AC Ph-N) |
|
Accuracy: 1% of full scale Average sensing |
|
|
Supported topologies: 3 Phase 4wire Single phase 2 wire 3 phase 3 wire 2 Phase 3 wire L1 & L2 2 Phase 3 wire L1 & L3 |
|
| Mains Input |
Range: 15V - 277(ph-N) (+20%) 50Hz - 60Hz |
|
Accuracy: 1% of full scale Average sensing |
|
|
Supported topologies: 3 Phase 4wire Single phase 2 wire 3 phase 3 wire 2 Phase 3 wire L1 & L2 2 Phase 3 wire L1 & L3 |
|
| CT’ s |
Burden: 0.5VA |
|
Primary rating: 1A - 6000A (user selectable) |
|
|
Secondary rating: 5A secondary |
|
|
Accuracy of measurement: 1% of full load rating (when using 0.5% or better CTs) Lower class CTs will reduce the overall accuracy of the reading. |
|
|
Recommendations: Class 1 required for instrumentation Protection class required if using for protection. |
|
| Magnetic Pickup |
Voltage range : +/- 0.5V minimum (during cranking) to 70V Peak |
|
Frequency range: 10, 000 Hz (max) |
|
| Relay Outputs |
Fuel: 16 Amp DC at supply voltage |
|
Start: 16 Amp DC at supply voltage |
|
|
Auxiliary outputs 1, 2, 3: 5 Amp DC at supply voltage |
|
| Dimensions |
Overall: 240mm x 172 mm x 57mm (9 ½ “ x 6 ¾ ” x 2 ¼ ” ) |
|
Panel cut-out: 220mm x 160mm ( 8.7” x 6.3” ) Max panel thickness 8mm ( 0.3” ) |
| HS Code: | 8503009090 |
|---|---|
| Trademark: | DSE |
| Model NO.: | 5220 |
| Productivity: | 1, 000 PCS/Month |
| Unit Price: | US $ 0-1000/ Piece |
| Shipment Terms: | by Air/ by Sea |
| Origin: | Chongqing, China |
| Packing: | Carton Box |
| Gross Weight: | 1kg |
| Package Size: | 290mm*180mm*65mm |
| Panel Cut-out: | 220mm*160mm |
| Color: | Black |
| Display: | LED & LCD |
| Application Range: | Gas & Diesel Generator Started With Battery |
| Power Range: | Above 10kw |
| Package: | Carton Box |
| in Stock: | Yes |
| Warranty: | 1 Year or Cumulative 1000-Hour-Operating Time |
| Export Markets: | North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe |
| Company: | Chongqing Boce Technology Co., Ltd. |
Most Popular
-

Hart Module for Pressure Sensor SE62H
Hart module SE62H Introduction: Input: All of ... -

Alternator 40A
Rared Voltage: 12V Rared output current: 40A ... -

Operating Device for Steam Turbine
We could offer Operating Device and other ...
-

Digital Laser Tachometer (DT-2234C+)
DT-2234c+: Display: 5 Digits, 18MM Test Range: ... -

Alternator (5-1250kVA)
Specifications Alternator, Brushless Alternator, ... -

101k Manual Diesel Generator Control Module
This model DACTS101k is a diesel control module. ...
-

Gas Generator Spark Plug K10P7(Jenbacher 351000)
Natural gas generator spark plug, used to replace ... -

Automatic Voltage Regulator for Caterpiller Generator (VR6)
Specifications Refer to Table 1 for the ... -

Rare Earth Permanent Magnet Generator
Rare earth permanent magnet generator Permanent ...
-

101KTR Manual Diesel Control Module
This model DACTS101k is a diesel control module. ... -

Uvr6 for Mecc Alte Alternator
General characteristics The UVR6 type voltage ... -

Brushless Alternator (JDG Series)
Specifications 1) Brushless Synchronous A. C. ...
-

Alternator 60A
Rared Voltage: 12V Rared output current: 60A ... -

Alternator 120A
Rared Voltage: 12V Rared output current: 120A ... -

Solar Module (GP/M/72/295W Module Series)
Our solar modules have these characteristics, ...
Quick Products |
Inquiry Basket (